Home • Products • Valves & Volume control dampersIris dampers • IRIS
B03  •  Iris dampersdownloads

IRIS

Galvanized steel IRIS air volume control damper of the diaphragm type with pressure measuring points

Available in range from Ø80 up to Ø800 mm

Application

  • For air volume control and measurement in ventilation and air conditioning systems.
  • The diaphragm valve ensures a perfect accordance between the diameter indication on the handle and the opening of the valve

Material

  • Galvanized steel

Composition

  • Body and valve made of galvanized sheet steel
  • Plastic regulating nut with plastic key
  • Measuring point on either side of the valve for connection of manometer
  • Sticker with selection graph, mentioning the air volume at the different opening positions of the valve and the according pressure level
  • Flexible joints for air tightness when placed inside the duct

Mounting

  • To be mounted in between two ducts according to mounting instructions
  • To be set on desired air volume according to set-table (joined with each damper)

Text for tender

  • The air volume control dampers shall be of the circular diaphragm type, suitable for medium and high pressure systems. They shall be made of galvanized sheet steel
  • ATC Type IRIS

Order example

IRIS 125

 

  • IRIS : Type of damper
  • 125 : Connection diameter

Articles

Article number Type Diameter [mm]
  B030101080000IRIS 80 80
  B030101100000IRIS 100 100
  B030101125000IRIS 125 125
  B030101150000IRIS 150 150
  B030101160000IRIS 160 160
  B030101200000IRIS 200 200
  B030101250000IRIS 250 250
  B030101315000IRIS 315 315
  B030101400000IRIS 400 400
  B030101500000IRIS 500 500
  B030101630000IRIS 630 630
  B030101800000IRIS 800 800

Dimensions

ød [mm]

øD [mm]

A [mm]

L [mm]

80

79

125

35

120

100

99

165

30

110

125

124

188

30

110

160

159

230

30

110

150

149

230

30

110

200

199

285

30

110

250

249

335

40

132

315

314

410

40

132

400

398

525

50

155

500

498

655

50

170

630

628

815

50

170

800

798

1015

100

270

K-factor

P K
Ø100 Ø125 Ø160 Ø200 Ø250 Ø315 Ø400
1 10.5 14.0 21.3 31.9 49.4 95.4 131
2 8.0 10.1 14.9 22.7 38.3 68.7 101
3 6.3 8.1 11.7 17.9 32.9 54.0 79.9
4 5.2 6.7 9.2 14.7 27.9 45.8 69.2
5 4.5 5.4 8.1 12.3 23.6 37.0 57.5
6 3.6 4.7 7.0 11.0 19.9 30.9 46.9
7 3.0 4.2 5.7 9.3 16.8 26.8 40.6
8 2.5 3.6 4.9 7.8 13.9 23.0 35.4
9 1.9 2.9 4.1 6.5 11.2 19.0 30.1
10 1.6 2.2 3.4 5.5 8.1 15.2 24.2

Notes

  • P = valve position

Pressure losses and sound levels

Dimensions

IRIS

ød [mm]

øD [mm]

A [mm]

L [mm]

80

79

125

35

120

100

99

165

30

110

125

124

188

30

110

150

149

230

30

110

160

159

230

30

110

200

199

285

30

110

250

249

335

40

132

315

314

410

40

132

400

398

525

50

155

500

498

655

50

170

630

628

815

50

170

800

798

1015

100

270

B03.010  •  Subject to technical modification
downloads
Requesting information. Please wait a moment...

Requesting information. Please wait a moment...
PRODUCTS


Requesting information. Please wait a moment...