Other Countries
Pricelist request
Copyright
Group Head Quarters • English
Ethics Policy
Home • Products • Fireproof productsFire dampers • CR120+BLFT24
E01  •  Motorized circular fire dampers EI120Sdownloads

CR120+BLFT24

Circular fire dampers with a fire resistance of 120 minutes. When the temperature in the damper rises above 72 °C the damper will close. When closed, the expanding material around the fireblade will assure a fire and air-tight seal against hot air and smoke. The tunnel is made out of galvanized steel. The CR120 + BLFT24 fire dampers have a automatic operating mechanism with actuator, with indication of the blade position. An end and begin of range switch is included within the actuator.

Application

  • Fire compartimentation
  • To close and seal off ventilation ducts in case of fire
  • For air temperatures of -10°C up to temperature of fusible link
  • For air with RV 0-96%
  • Range of Ø100 up to Ø315 mm
  • For Ø355 up to Ø630 see type CR2

Material

  • Galvanized steel

Composition

  • Galvanized steel tunnel
  • Fibersilicate fireproof blade
  • Intumescent strip
  • Belimo BLFT24 Actuator with thermo-electrical fuse

Mounting

  • To be inserted in fire resistant walls or floors and to be fixed according to the mounting instruction delivered with the valves.
  • To be connected with round air ducts
  • To be electrically wired to the fire detection system or building system

Certification

  • Approval according to EN 1366-2
  • CE-marked

Certification

  • Classified EI120(ve,ho i<->o)S at 500Pa according EN 13501-3 in ridid wall and rigid floor.
  • Classified EI60(ve i<->o)S at 500Pa according EN 13501-3 in flexible wall.
  • Certified with test report Efectis 09-A-087+Ext.10/1
  • Airtight EN 1751 class B, Class C upon request
  • CE marked

Accessories

  • Fire resistant plaster BP

Other available products

  • For bigger sizes see CR2 + B(L)FT24

Text for tender

  • The fire dampers shall be of the round type with a fire resistance of 120 minutes, certified according to EN13501-3 . They will consist of a galvanized steel tunnel and fireproof fiber silicate valve. The control mechanism will be automatically operated by means of an actuator and shall have a blade position indicator and thermo-electrical link of 72 °C
  • ATC type CR120 + BLFT24

Order example

  • CR120 + BLFT24, 160

 

Explanation

CR120 = Round fire damper with fire resistance of 120 minutes

BLFT24 = Actuator 24V with thermo-electrical fuse

160 = Connection diameter

Articles

Article number Type Diameter [mm] Qv (veff 5 m/s) [m3/h] Weight [kg]
  E010150100000CR120+BLFT24 100 100 141 3
  E010150125000CR120+BLFT24 125 125 221 3.20
  E010150160000CR120+BLFT24 160 160 362 3.50
  E010150200000CR120+BLFT24 200 200 566 4
  E010150250000CR120+BLFT24 250 250 884 4.70
  E010150315000CR120+BLFT24 315 315 1403 5.60

Quick selection

Dia v 3 4 5 6 7 8
100 Qv 85 113 141 170 198 226
veff 5 6.70 8.40 10 11.70 13.40
Ps 12 18 25 34 44 56
Lw 25 30 34 37 40 42
125 Qv 133 177 221 265 309 353
veff 4.50 6 7.40 8.90 10.40 11.90
Ps 10 14 19 25 33 41
Lw 27 31 35 38 41 43
160 Qv 217 290 362 434 507 579
veff 4.10 5.40 6.80 8.10 9.50 10.80
Ps 8 11 15 19 25 31
Lw 28 33 37 40 42 45
200 Qv 339 452 566 679 792 905
veff 3.80 5.10 6.30 7.60 8.90 10.20
Ps 8 10 12 16 20 24
Lw 29 34 38 41 44 46
250 Qv 530 707 884 1060 1237 1414
veff 3.60 4.80 6 7.20 8.40 9.70
Ps 7 9 11 13 16 20
Lw 30 35 39 42 45 47
315 Qv 842 1122 1403 1683 1964 2244
veff 3.50 4.60 5.80 7 8.10 9.30
Ps 6 8 9 11 13 16
Lw 32 36 40 43 46 48

Dia v 3 4 5 6 7 8
100 Qv 85 113 141 170 198 226

Veff

5 6.70 8.40 10 11.70 13.40
Ps 12 18 25 34 44 56
Lw 25 30 34 37 40 42
125 Qv 133 177 221 265 309 353

Veff

4.50 6 7.40 8.90 10.40 11.90
Ps 10 14 19 25 33 41
Lw 27 31 35 38 41 43
160 Qv 217 290 362 434 507 579

Veff

4.10 5.40 6.80 8.10 9.50 10.80
Ps 8 11 15 19 25 31
Lw 28 33 37 40 42 45
200 Qv 339 452 566 679 792 905

Veff

3.80 5.10 6.30 7.60 8.90 10.20
Ps 8 10 12 16 20 24
Lw 29 34 38 41 44 46
250 Qv 530 707 884 1060 1237 1414

Veff

3.60 4.80 6 7.20 8.40 9.70
Ps 7 9 11 13 16 20
Lw 30 35 39 42 45 47
315 Qv 842 1122 1403 1683 1964 2244

Veff

3.50 4.60 5.80 7 8.10 9.30
Ps 6 8 9 11 13 16
Lw 32 36 40 43 46 48

Symbols and specifications

  • v = Air velocity in the duct in m/s
  • Qv = Air volume in m³/h
  • veff = Effective velocity through the damper in m/s
  • Ps = Static pressure in Pa
  • Lw = Acoustic power in dB(A)
  • Dia = Duct diameter in mm

Dimensions

CR120+BLFT24

ØD [mm]

ØD-1 [mm]

1/2ØD+70 [mm]

100

100

99

120

125

125

124

132.5

160

160

159

150

200

200

199

170

250

250

249

195

315

315

314

228