Other Countries
Pricelist request
Copyright
Group Head Quarters • English
Ethics Policy
Home • Products • FansFan casings • MVB MAC
I02  •  Double skinned ventilation boxesdownloads

MVB MAC

Doubble skinned ventilation box with a constant flow motor

Application

  • Ventilation of medium and large rooms
  • Can be used for air intake as well as exhaust
  • Disigned to meet the highest standards in thermal and acoustic insulation

Composition

  • Structure with aluminium profiles
  • Corners in reinforced polyamide
  • Interchangeable, removable panels allowing any type of installation
  •  Outer layer: prelacquered steel plate (RAL 7035) with protection sheet
  • Insulation : high-quality glass wool 25 mm M0
  •  Inside in galvanized steel plate
  • Internal elements access panel equipped with security bolt
  • Built-in nuts for fastening on floor, wall or ceiling
  • Round connections with lip seals
  •  Sliding rails with lip seals for filter, thickness 100 mm for filter type: see options

Fan

  • Double inlet centrifugal fan, forward curved blades
  • Supply: 230Vac 1ph or 400Vac 3ph 
  • Insulation class B motor with thermal protection 
  • Motor-fan assembly mounted on anti-vibration mounts
  • Flexible connection between fan and exhaust panel

Accessories

  • Seed controller BTRN
  • Roof MVX TCB for ouside use
  • Canopy with guard MVX AGC
  • Damper to be motorised MVX RM
  • Flexibel connectors MVX MTS
  • Safety switch MVX IPC
  • Filter G4 or F7
  • Electrical heating module MVX BE
  • Hot water heating module MVX BC
  • Chilled water module MVX BF
  • Direct expansion coil module MVX DX

Order example

  • MVB 2000

MVB: type of fan

2000: maximum air volume

Articles

Article number Type
  I020401160000MVB 1600

Air performance data

Qv [m³/h]

50 Pa 100 Pa 150 Pa 200 Pa 250 Pa 300 Pa 350 Pa 400 Pa 450 Pa

1000

950 900 875 825 775 675 500 - -

1500

1600 1500 1450 1350 875 - - - -

1600

1750 1700 1600 1540 1470 1400 1300 1220 1100

2000

2200 2100 2000 1800 1350 - - - -

3000

- - 2900 2850 2750 2650 2450 - -

4000

4200 4100 4050 3800 3600 3400 3000 - -

4350

- - - - - 4150 4050 3850 3500

6500

- - 6800 6700 6550 5950 - - -

6000

6550 6450 6250 6100 5800 5500 5300 5000 4700

The MVB fan may never be used with free inlet! There should be a minimal counterpressure as shown in the table above.

Measure the current at first starting!

Technical data

Type Size Voltage [V] Power [W] Current [A] Transformer controller Sound level [dB(A)]
PSA NSC3
1000 4a 1 x 230 260 1.30 BTRN-1-1 62 25
1500 4b 1 x 230 147 2.10 BTRN-1-2 65 28
1600 4b 1 x 230 1000 4.80 BTRN-1-5 78 41
2000 4b 1 x 230 300 2.30 BTRN-1-3 72 35
3000 5 1 x 230 373 5 BTRN-1-7 77 39
4000 5 1 x 230 550 6.80 BTRN-1-7 75 37
4350 6 1 x 230 550 6.50 BTRN-1-7 71 32
6500 7 1 x 230 1100 10 BTRN-1-13 76 35

6000

7

3 x 400

1500

4.70

BTRN-4-6

84

43

PSA :

Soundpower at the extractionside of the fan.

NSC3 : Sound pressure at 3 meter distance under the unit in a free space.

Dimensions

A [mm]

B [mm] C [mm] Ø [mm]

Kg

1000 445 445 445 250 27
1500 445 445 445 315 32
1600 445 445 445 315 33
2000 445 445 445 315 34
3000 545 545 545 400 46
4000 545 545 545 400 53
4350 645 645 645 450 69
6500 745 745 745 500 89
6000 745 745 745 500 87
I.02.040.1B  •  Subject to technical modification
downloads
Requesting information. Please wait a moment...

Requesting information. Please wait a moment...
PRODUCTS


Requesting information. Please wait a moment...