MVB MACDoubble skinned ventilation box with a constant flow motor Application
- Ventilation of medium and large rooms
- Can be used for air intake as well as exhaust
- Disigned to meet the highest standards in thermal and acoustic insulation
Composition
- Structure with aluminium profiles
- Corners in reinforced polyamide
- Interchangeable, removable panels allowing any type of installation
- Outer layer: prelacquered steel plate (RAL 7035) with protection sheet
- Insulation : high-quality glass wool 25 mm M0
- Inside in galvanized steel plate
- Internal elements access panel equipped with security bolt
- Built-in nuts for fastening on floor, wall or ceiling
- Round connections with lip seals
- Sliding rails with lip seals for filter, thickness 100 mm for filter type: see options
Fan
- Double inlet centrifugal fan, forward curved blades
- Supply: 230Vac 1ph or 400Vac 3ph
- Insulation class B motor with thermal protection
- Motor-fan assembly mounted on anti-vibration mounts
- Flexible connection between fan and exhaust panel
Accessories
- Seed controller BTRN
- Roof MVX TCB for ouside use
- Canopy with guard MVX AGC
- Damper to be motorised MVX RM
- Flexibel connectors MVX MTS
- Safety switch MVX IPC
- Filter G4 or F7
- Electrical heating module MVX BE
- Hot water heating module MVX BC
- Chilled water module MVX BF
- Direct expansion coil module MVX DX
Order example
MVB: type of fan
2000: maximum air volume |
ArticlesAir performance data
|
Qv [m³/h] |
| 50 Pa |
100 Pa |
150 Pa |
200 Pa |
250 Pa |
300 Pa |
350 Pa |
400 Pa |
450 Pa |
1000 |
950 |
900 |
875 |
825 |
775 |
675 |
500 |
- |
- |
1500 |
1600 |
1500 |
1450 |
1350 |
875 |
- |
- |
- |
- |
1600 |
1750 |
1700 |
1600 |
1540 |
1470 |
1400 |
1300 |
1220 |
1100 |
2000 |
2200 |
2100 |
2000 |
1800 |
1350 |
- |
- |
- |
- |
3000 |
- |
- |
2900 |
2850 |
2750 |
2650 |
2450 |
- |
- |
4000 |
4200 |
4100 |
4050 |
3800 |
3600 |
3400 |
3000 |
- |
- |
4350 |
- |
- |
- |
- |
- |
4150 |
4050 |
3850 |
3500 |
6500 |
- |
- |
6800 |
6700 |
6550 |
5950 |
- |
- |
- |
6000 |
6550 |
6450 |
6250 |
6100 |
5800 |
5500 |
5300 |
5000 |
4700 |
The MVB fan may never be used with free inlet! There should be a minimal counterpressure as shown in the table above. |
Measure the current at first starting! |
Technical data
| Type |
Size |
Voltage [V] |
Power [W] |
Current [A] |
Transformer controller |
Sound level [dB(A)] |
| PSA |
NSC3 |
| 1000 |
4a |
1 x 230 |
260 |
1.30 |
BTRN-1-1 |
62 |
25 |
| 1500 |
4b |
1 x 230 |
147 |
2.10 |
BTRN-1-2 |
65 |
28 |
| 1600 |
4b |
1 x 230 |
1000 |
4.80 |
BTRN-1-5 |
78 |
41 |
| 2000 |
4b |
1 x 230 |
300 |
2.30 |
BTRN-1-3 |
72 |
35 |
| 3000 |
5 |
1 x 230 |
373 |
5 |
BTRN-1-7 |
77 |
39 |
| 4000 |
5 |
1 x 230 |
550 |
6.80 |
BTRN-1-7 |
75 |
37 |
| 4350 |
6 |
1 x 230 |
550 |
6.50 |
BTRN-1-7 |
71 |
32 |
| 6500 |
7 |
1 x 230 |
1100 |
10 |
BTRN-1-13 |
76 |
35 |
6000 |
7 |
3 x 400 |
1500 |
4.70 |
BTRN-4-6 |
84 |
43 |
| PSA : |
Soundpower at the extractionside of the fan. |
| NSC3 : |
Sound pressure at 3 meter distance under the unit in a free space. |
Dimensions
|
A [mm] |
B [mm] |
C [mm] |
Ø [mm] |
Kg |
| 1000 |
445 |
445 |
445 |
250 |
27 |
| 1500 |
445 |
445 |
445 |
315 |
32 |
| 1600 |
445 |
445 |
445 |
315 |
33 |
| 2000 |
445 |
445 |
445 |
315 |
34 |
| 3000 |
545 |
545 |
545 |
400 |
46 |
| 4000 |
545 |
545 |
545 |
400 |
53 |
| 4350 |
645 |
645 |
645 |
450 |
69 |
| 6500 |
745 |
745 |
745 |
500 |
89 |
| 6000 |
745 |
745 |
745 |
500 |
87 |
|