Backward curved centrifugal fan. The range comprise 11 sizes with different speeds and air volumes from 900 up to 9600 m3/h

Application

  • These fans are designed for direct or ducted ventilation in residential, commercial and industrial buildings

Composition

  • Housing made of seawater resistant aluminium AlMg3
  • Integrated thermal contact
  • Maintenance-free, long-life ball bearings
  • Swivel mounted fan section
  • Integrated isolator switch

Accessories

  • Transformer speed controllers type BTRN
  • Roof socket RAC-I
  • Roof socket RC-I
  • Flexible connector RFC
  • Matching flange RIF
  • Backdraught shutter RAS

Order example

  • ARF-S 220 E2

ARF= Type of fan

220= Size

E= 1x230V

2= 2800rpm

Articles

Article number Type Type Voltage [V] Speed [rpm] Qv at 100 Pa [m3/h] Power [W]
  I030300022022ARF-S 220 E2 220 E2 230 2800 640 100
  I030300025022ARF-S 250 E2 250 E2 230 2800 1115 190
  I030300025024ARF-S 250 E4 250 E4 230 1400 325 60
  I030300028022ARF-S 280 E2 280 E2 230 2800 1520 290
  I030300031524ARF-S 315 E4 315 E4 230 1400 1305 130
  I030300035524ARF-S 355 E4 355 E4 230 1400 2475 300
  I030300035544ARF-S 355 D4 355 D4 400 1400 2360 265
  I030300040024ARF-S 400 E4 400 E4 230 1400 3715 540
  I030300040044ARF-S 400 D4 400 D4 400 1400 3620 500
  I030300045044ARF-S 450 D4 450 D4 400 1400 5345 870
  I030300050044ARF-S 500 D4 500 D4 400 1400 7620 1600

Air performance data

 

Qv [m³/h]

0Pa

100Pa

200Pa

300Pa

400Pa

500Pa

600Pa

700Pa

ARF-S 220 E2

780 640

500

305

60

-

-

-

ARF-S 250 E2

1255

1115

935

750

530

290

-

-

ARF-S 250 E4

645

325

-

-

-

-

-

-

ARF-S 280 E2

1755

1520

1240

945

655

470

280

-

ARF-S 315 E4

1695

1305

660

-

-

-

-

-

ARF-S 355 E4

2890

2475

1980

1325

-

-

-

-

ARF-S 400 E4

4160

3715

3195

2565

1530

-

-

-

ARF-S 355 D4

2775

2360

1850 990

-

-

-

-

ARF-S 400 D4

4035

3620

3160 2530

1625

-

-

-

ARF-S 450 D4

5835

5345

4815

4180

3375

2330

510

-

ARF-S 500 D4

8050

7620

7110 6590 6000

5210

4245 2410

Performance curve

Performance curve

Technical data

U [V] P [W] I [A] tm [°C] ta [°C] n [rpm] Lwa [dB(A)]
Lwa 5 Lwa 6
ARF-S 220 E2 1 x 230 100 0.50 70 70 2532 70 73
ARF-S 250 E2 1 x 230 190 0.90 50 50 2620 76 81
ARF-S 250 E4 1 x 230 60 0.30 50 50 1343 61 65
ARF-S 280 E2 1 x 230 290 1.30 60 60 2528 80 83
ARF-S 315 E4 1 x 230 120 0.60 60 60 1317 68 70
ARF-S 355 E4 1 x 230 280 1.40 70 70 1337 75 76
ARF-S 400 E4 1 x 230 520 2.80 50 50 1384 77 81
ARF-S 355 D4 3 x 400 260 0.60 60 60 1370 73 77
ARF-S 400 D4 3 x 400 500 1.20 70 70 1370 77 81
ARF-S 450 D4 3 x 400 870 1.80 60 60 1370 81 85
ARF-S 500 D4 3 x 400 1600 3.90 55 55 1420 86 89

ta = Ambient Temperature

tm = Medium Temperature

LWA5=Inlet - sound power level [dB(A)]

LWA6=Outlet - sound power level [dB(A)]

The sound power levels are measured according to DIN 45635 part 2 & 38

Technical data

U [V]

P [W] I [A]

SCT

ŋt [%]

tm [°C] tu [°C] to [°C] n [rpm]

Lwa [dB(A)]

Lwa 5 Lwa 6 Lwa 2

ARF-S 220 E2

1 x 230 100 0.50 BTRN 1-S1 31 70 70 -25 2532 70 73 -

ARF-S 250 E2

1 x 230 190 0.90 BTRN 1-S1 34 50 50 -25 2620 76 81 -

ARF-S 250 E4

1 x 230 60 0.30 BTRN 1-S1 16 50 50 -25 1343 61 65 -

ARF-S 280 E2

1 x 230 290 1.30 BTRN 1-1 30 60 60 -25 2528 80 83 -

ARF-S 315 E4

1 x 230 120 0.60 BTRN 1-S1 34 60 60 -25 1317 68 70 -

ARF-S 355 E4

1 x 230

280

1.40

BTRN 1-2

40 70 70 -25 1337 75 76 -

ARF-S 400 E4

1 x 230 520 2.80 BTRN 1-3 43 50 50 -25 1384 77 81 -

ARF-S 355 D4

3 x 400 260 0.60 BTRN 4-2 39 60 60 -30 1370 73 77 -

ARF-S 400 D4

3 x 400 500 1.20 BTRN 4-2 44 70 70 -30 1370 77 81 -

ARF-S 450 D4

3 x 400 870 1.80 BTRN 4-2 44 60 60 -30 1370 81 85 -
ARF-S 500 D4 3 x 400 1600 3.90 BTRN 4-4 45 55 55 -30 1420 86 89 -

SCT = transformer controller

ŋt = maximum total efficiency

tm = maximum air temperature

tu = maximum ambient temperature

to = minimum operating temperature

Lwa 2 = Casing sound power level

Lwa 5 = Sound power level @inlet

Lwa 6 = Sound power level @outlet

The sound power levels are measured according to DIN 45635 part 2 & 38

Dimensions

 

A [mm]

B [mm]

C [mm]

D [mm]

E [mm]

F [mm]

G [mm]

H [mm]

I [mm]

J[mm]

[kg]

ARF-S 220 E2

235 335 439 245

92.5

92.5 245 Ø213 308 4xØ9 7.4

ARF-S 250 E2

235 335 439 245

92.5

92.5 245 Ø213 308 4xØ9 8.1

ARF-S 250 E4

235 335 439 245

92.5

92.5 245 Ø213 308 4xØ9 7.6

ARF-S 280 E2

289 435 576 330

135

135 330 Ø286 408 4xØ9 11.5

ARF-S 315 E4

289 435 578 330

135

135 330 Ø286 408 4xØ9 11

ARF-S 355 E4

399 595 795 450

195.5

195.5 450 Ø438 570 4xØ11 24.2

ARF-S 400 E4

399 595 795 450

195.5

195.5 450 Ø438 570 4xØ11 27.2

ARF-S 355 D4

399 595 795 450

195.5

195.5 450 Ø438 570 4xØ11 23.6

ARF-S 400 D4

399 595 795 450

195.5

195.5 450 Ø438 570 4xØ11 27.2

ARF-S 450 D4

494 665 916 535

230.5

230.5 535 Ø438 640 4xØ9 38.5

ARF-S 500 D4

494

665 916 535

230.5

230.5 535 Ø438 640 4xØ9 47