Application
- Shower rooms
- Bathrooms
- Kitchens
- Utility rooms
Construction
- The all plastic casing provides a long lasting, robust and non corrosive construction.
- The units have been constructed from shock proof, heat resistant white plastic, with both motors and impellers mounted within the length of the unit casing.
- All units are IPX4 protection and are splash proof as required by current regulations.
Fan/Impeller
- Mixed flow impellers shall be provided with fixed blade angles to meet the required duty.
- The impeller construction shall comprise of white plastic.
Motor
- Motors are to be double insulated with in-built thermal overload protection, with sealed for life bearings, suitable for operating temperatures of up to +60ÂșC.
- Motors are to be wired to a terminal box mounted on the outside of the unit casing.
Features and benefits
- The Multiflow SMT is a range of in-line mixed flow fans with a compact profile which offers excellent pressure development characteristics, designed specifically for use with rigid or flexible ductwork for a wide variety of residential and commercial applications
Accessories
- Silencers
- Heater batteries
- Fast clamps
|
ArticlesAirflow table
| |
RPM |
0 |
25 |
50 |
75 |
100 |
125 |
150 |
175 |
200 |
225 |
250 |
| SMT100 |
2300 |
0.070 |
0.067 |
0.063 |
0.059 |
0.053 |
0.038 |
0.024 |
0.014 |
- |
- |
- |
| SMT100 |
1700 |
0.056 |
0.05 |
0.042 |
0.028 |
0.017 |
0.007 |
- |
- |
- |
- |
- |
| SMT125 |
2300 |
0.076 |
0.071 |
0.066 |
0.059 |
0.039 |
0.022 |
0.012 |
- |
- |
- |
- |
| SMT125 |
1700 |
0.055 |
0.049 |
0.043 |
0.022 |
0.008 |
- |
- |
- |
- |
- |
- |
| SMT150 |
2700 |
0.131 |
0.127 |
0.122 |
0.118 |
0.113 |
0.108 |
0.102 |
0.095 |
0.082 |
0.029 |
0.014 |
| SMT150 |
2000 |
0.106 |
0.102 |
0.098 |
0.093 |
0.088 |
0.080 |
0.066 |
0.037 |
0.019 |
0.004 |
- |
| SMT200 |
2700 |
0.233 |
0.224 |
0.214 |
0.202 |
0.189 |
0.174 |
0.152 |
0.104 |
- |
- |
- |
| SMT200 |
2000 |
0.171 |
0.14 |
0.118 |
0.097 |
- |
- |
- |
- |
- |
- |
- |
Technical specifications
| |
Motor Electrical Data |
DBA @ 3m |
| FLC Amps |
Input Watts |
| SMT100 |
0.18 |
30 |
42 |
| SMT100 |
0.10 |
18 |
35 |
| SMT125 |
0.18 |
30 |
43 |
| SMT125 |
0.10 |
18 |
35 |
| SMT150 |
0.36 |
80 |
52 |
| SMT150 |
0.27 |
60 |
48 |
| SMT200 |
0.34 |
85 |
50 |
| SMT200 |
0.24 |
55 |
39 |
Dimensional data
| |
A |
B |
C |
D |
E |
F |
G |
KG |
| SMT100 |
315 |
235 |
115 |
98 |
180 |
232 |
130 |
3 |
| SMT125 |
280 |
235 |
115 |
122 |
180 |
232 |
130 |
3 |
| SMT150 |
294 |
265 |
115 |
147 |
192 |
240 |
130 |
3 |
| SMT200 |
354 |
265 |
140 |
197 |
230 |
280 |
142 |
4 |
|