ArticlesSelection diagrams 1= HRS H 400 supply 2= HRS H 400 exhaust 3= HRS H 700 supply
4= HRS H 700 exhaust 5= HRS H 1000 supply 6= HRS H 1000 exhaust
7= HRS H 1500 supply 8= HRS H 1500 exhaust 9= HRS H 1900 supply
10= HRS H 1900 exhaust Technical data
With electrical heater |
400E |
700E |
1000E |
1500E |
1900E |
Heater |
phase/voltage |
[50Hz/VAC] |
~1, 230 |
~1, 230 |
~3, 400 |
~3, 400 |
~3, 400 |
power cons. |
[kW] |
2,0 |
3 |
6,0 |
9,0 |
15,0 |
Pre-heater for heat exchanger |
- |
[kW] |
1,0 |
1,2 |
- |
- |
- |
Fans |
phase/voltage |
[50Hz/VAC] |
~1, 230 |
~1, 230 |
~1, 230 |
~1, 230 |
~1, 230 |
exhaust |
power/current |
[kW/A] |
0,162/0,70 |
0,230/1,0 |
0,230/1,0 |
0,356/1,55 |
0,669/2,95 |
fan speed |
[min-1] |
2100 |
2000 |
2650 |
2750 |
2830 |
supply |
power/current |
[kW/A] |
0,199/0,87 |
0,230/1,0 |
0,226/0,98 |
0,369/1,6 |
0,669/2,95 |
fan speed |
[min-1] |
1850 |
2000 |
2650 |
2750 |
2830 |
Motor protection class |
- |
[W/A] |
IP-54/IP-44 |
IP-54 |
IP-44 |
IP-44 |
IP-54 |
Thermal efficiency |
- |
- |
60% |
60% |
54% |
54% |
60% |
Max power consumption |
- |
[kW/A] |
3,36/14,61 |
4,66/15,91 |
6,456/10,64 |
9,725/16,14 |
16,34/27,55 |
Automatic control |
- |
- |
integrated |
integrated |
integrated |
integrated |
integrated |
Filter class |
exhaust |
- |
EU3 |
EU3 |
EU5 |
EU5 |
EU5 |
supply |
- |
EU5 |
EU5 |
EU5 |
EU5 |
EU5 |
Thermal insulation |
- |
[mm] |
50 |
50 |
50 |
50 |
50 |
Weight |
- |
[kg] |
48,0 |
57,0 |
152,0 |
152,0 |
214,0 |
With water heater |
400W |
700W |
1000W |
1500W |
1900 W |
Heater |
power |
[kW] |
2,7 |
4,7 |
6,75 |
10,12 |
12,82 |
water temp. Tin/Tout |
[°C] |
80/60 |
80/60 |
80/60 |
80/60 |
80/60 |
water flow rate |
[l/s] |
0,03 |
0,06 |
0,08 |
0,12 |
0,16 |
water pressure drop |
[kPa] |
2,47 |
4,9 |
1,8 |
3,3 |
4,70 |
kvs value |
[mł/h] |
0,7 |
1 |
2,2 |
2,4 |
2,7 |
Pre-heater for heat exchanger |
- |
[kW] |
1 |
1,2 |
- |
- |
- |
Fans |
phase/voltage |
[50Hz/VAC] |
~1, 230 |
~1, 230 |
~1, 230 |
~1, 230 |
~1, 230 |
exhaust |
power/current |
[kW/A] |
0,161/0,7 |
0,233/1,0 |
0,214/0,93 |
0,351/1,52 |
0,669/2,95 |
fan speed |
[min-1] |
2100 |
2000 |
2650 |
2750 |
2830 |
supply |
power/current |
[kW/A] |
0,194/0,85 |
0,222/0,97 |
0,228/1,0 |
0,368/1,6 |
0,669/2,95 |
fan speed |
[min-1] |
1850 |
2000 |
2650 |
2750 |
2830 |
Motor protection class |
- |
[W/A] |
IP-54 |
IP-54 |
IP-44 |
IP-44 |
IP-55 |
Thermal efficiency |
- |
- |
60% |
60% |
54% |
54% |
60% |
Max power consumption |
- |
[kW/A] |
1,355/5,90 |
1,655/7,19 |
0,442/1,98 |
0,72/3,12 |
1,338/5,9 |
Automatic control |
- |
- |
integrated |
integrated |
integrated |
integrated |
integrated |
Filter class |
exhaust |
- |
EU3 |
EU3 |
EU5 |
EU5 |
EU5 |
supply |
- |
EU5 |
EU5 |
EU5 |
EU5 |
EU5 |
Thermal insulation |
- |
[mm] |
50 |
50 |
50 |
50 |
50 |
Weight |
- |
[kg] |
48,0 |
57,0 |
152,0 |
152,0 |
216,0 |
| Air flow temperature range from -20°C to +40°C |
| Designed for operation indoors only |
| Thermal efficiency measured at indoor conditions of +20°C/60% and outdoor conditions of -20°C/90% |
Dimensions
|
L [mm] |
W [mm] |
H [mm] |
øD [mm] |
H1 [mm] |
F [mm] |
| HRS H 400HE |
1000 |
354 |
670 |
160 |
30 |
30 |
| HRS H 400HW |
1170 |
354 |
670 |
160 |
30 |
30 |
| HRS H 700HE |
1170 |
504 |
690 |
250 |
30 |
40 |
| HRS H 700HW |
1320 |
504 |
690 |
250 |
30 |
40 |
| HRS H 1000HE |
1500 |
645 |
865 |
315 |
70 |
40 |
| HRS H 1000HW |
1500 |
645 |
865 |
315 |
70 |
40 |
| HRS H 1500HE |
1500 |
645 |
865 |
315 |
70 |
40 |
| HRS H 1500HW |
1500 |
645 |
865 |
315 |
70 |
40 |
| HRS H 1900HE |
1800 |
790 |
1050 |
400 |
70 |
65 |
HRS H 1900HW |
1800 |
790 |
1050 |
400 |
70 |
65 |
IV - Exhaust air fan PV - Supply air fan PR - Plate heat exchanger KE - Electrical heater
CWW - Optionally supplied water heater PE - Anti-freeze heater for heat exchanger PF - Filter for supply air (class EU5) IF - Filter for extract air (class EU3 or EU5) TJ - Temperature sensor for supply air TL - Temperature sensor for fresh air TE - Temperature sensor for extract air
TV - Optionally supplied antifrost sensor
T1 - Optionally supplied antifrost thermostat DTJ - Humidity + temperature sensor
P - Heat exchanger pressure switch M - By-pass damper
M1 - Optionally supplied mixing valve and motor |