RCF-IHeat recovery unit with aluminium crossflow exchanger. The range consists of 7 sizes in vertical and horizontal execution and covers an air flow range from 350 up to 3300 m³/h. Apart from heat recovery, many other configurations are available in terms of air treatment such as water- or electrical heating, cooling (water or DX) or filtration Application
- Ventilation and heat recovery of the exhausted air in commercial applications
- Air filtration
- Heating and cooling
- Mounting in false ceiling or standing
Composition
- Self-bearing 20 mm thick sandwich panels made of galvanized steel sheet for the external and internal surfaces and with injected polyurethane insulation
- Undulated filters class G3
- Double-intake radial fans
- Condensate drain pan
- Inspection from below, above and sideways according to the chosen configuration
Exchanger
- Crossflow type with aluminium plates with performances above 50% in winter operation with by-pass
Text for tender
-
Heat recovery unit with aluminium crossflow exchanger. The range consists of 7 sizes in vertical and horizontal execution and covers an air flow range from 350 up to 3300 m³/h. Apart from heat recovery, many other configurations are available in terms of air treatment such as water- or electrical heating, cooling (water or DX) or filtration.
- ATC type RCF-I
Order exampleRCF-I 33 A
Explanation
RCF-I = Type Heat recovery
33 = Nominal air flow 3300m³/h |
ArticlesTechnical data
| |
|
RCF-I 07 |
RCF-I 10 |
RCF-I 15 |
RCF-I 21 |
RCF-I 33 |
| Nominal airflow |
[m³/h] |
750 |
1000 |
1500 |
2100 |
3300 |
| Minimum airflow |
[m³/h] |
640 |
850 |
1275 |
1785 |
2800 |
| Static pressure exhaust (1) |
[Pa] |
256 |
211 |
223 |
146 |
267 |
| Total heating power (3) |
[kW] |
8.40 |
11.50 |
16.30 |
23.90 |
31 |
| Total cooling power (recovery+ compress.) (2) |
[kW] |
5.50 |
8 |
10.90 |
16.80 |
21.20 |
| Available heating power (3) |
[kW] |
1.90 |
3.30 |
3.30 |
6.60 |
3.50 |
| Available cooling power (2) |
[kW] |
1.10 |
2 |
2.30 |
4.10 |
4.20 |
| Efficiency (3) |
[%] |
51 |
56 |
55 |
58 |
52 |
| Absorbed power fans |
[kW] |
0.75 |
0.75 |
1.50 |
1.50 |
2.50 |
| Absorbed current fans |
[A] |
5 |
5 |
8.60 |
8.60 |
13.20 |
| Absorbed compressor power winter (3) |
[kW] |
1.20 |
1.70 |
2.60 |
3.40 |
3.80 |
| Absorbed compressor power summer (2) |
[kW] |
2.40 |
3 |
4 |
5.60 |
5.80 |
| Max. absorbed compressor current |
[A] |
10.90 |
14 |
6.70 |
9.70 |
11.10 |
| Total absorbed heating power (3) |
[kW] |
1.80 |
2.30 |
3.70 |
4.50 |
5 |
| Total absorbed cooling power (2) |
[kW] |
3 |
3.60 |
5.10 |
6.70 |
8 |
| Supply voltage |
[ph-V-Hz] |
1-230-50 |
1-230-50 |
3+N 400-50 |
3+N 400-50 |
3+N 400-50 |
| Sound pressure level @ 1m (6) |
[dB(A)] |
53 |
55 |
57 |
59 |
62 |
| Refrigerant |
- |
R407C |
R407C |
R407C |
R407C |
R407C |
| (1) Electrical supply fan 230V, nominal air flow, no accessories |
| (2) Air flow fresh air equal to air flow exhaust air, outside intake temperature air 34°C, 50% HR, ambient temperature 26°C, 50% HR |
| (3) Air flow fresh air equal to air flow exhaust air, outside intake temperature air -5°C, 80% HR, ambient temperature 20°C, 50% HR |
| (6) @ 1m distance in free field, fans connected to ducts |
Dimensions
| |
L |
W |
H |
[Kg] |
| [mm] |
[mm] |
[mm] |
| RCF-I 07 |
1500 |
1300 |
450 |
205 |
| RCF-I 10 |
1500 |
1300 |
450 |
218 |
| RCF-I 15 |
1800 |
1500 |
550 |
272 |
| RCF-I 21 |
1800 |
1500 |
550 |
298 |
| RCF-I 33 |
1800 |
1600 |
600 |
328 |
|