J02  •  Outdoor Unit AUHDdownloads

AUHDLO1PH

This outdoor unit heat pump type split single inverter can be connected to various types of indoor units such as tapes, floor/ceiling types, ... DC compressor ensures quiet operation and energy-saving and long life.

Brand

  • ATC / Gree

Product

  • Outdoor unit for general applications (cassettes, floor / ceiling,...)

Application

  • Cooling or heating of office rooms, living rooms, apartments, workshops ...

Function

  • Excellent performance thanks to D.C. Inverter technology

Refrigerant

  • R410a

Applicable indoor units

  • Type AKH 12 K3CI
  • Type AKH 18 K3CI
  • Type AKH 24 K3CI
  • Type AKH 42 K3CI
  • Type ATH 24 K3CI
  • Type ATH 42 K3CI
  • Type ATH 60 K3CI

Accessories

  • Wall mount (type WBAT2)
  • Condensation evacuation for wall suport (CTS and CTL)
  • PVC mouting blocks
  • Solid mounting blocks
  • MPR mounting blocks
  • Insulated copper pipes (TYP, PAIRCOIL)
  • Tape - white (WT50)

 

Articles

Article number Type Size Nominal cooling capacity [kW] Nominal heating capacity [kW]
  J023703094090AUHDLO1PH 09 2.63 2.93
  J023703094120AUHDLO1PH 12 3.51 3.80
  J023703094180AUHDLO1PH 18 5.27 6.39
  J023703094240AUHDLO1PH 24 7.03 7.17
  J023703094300AUHDLO1PH 30 8.79 9.49
  J023703094360AUHDLO1PH 36 10.19 11.50
  J023703094420AUHDLO1PH 42 11.89 13.18
  J023703094480AUHDLO1PH 48 14.00 15.50

Specifications

Inverter U-Match Unit AUHD12NK3C1O AUHD18NK3C1O AUHD24NK3C1O AUH30NK3C1O AUHD36NK3C1O AUHD42NK3C1O AUHD48NK3C1O AUHD42NM3C1O AUHD60NM3C1O

Nominal cooling (min-max)

kW 3,4 (1,6 - 3,6) 5,3 (1,3 - 5,8) 7,1 (2,0 - 8,3) 8,8 (2,7 - 9,1) 10,3 (3,0 - 13,0) 11,0 (3,5 - 13,0) 14,0 (5,0 - 14,3) 11,0 (3,5 - 13,0) 17,0 (4,0 - 17,5)

Nominal heating(min-max)

kW 3,8 (1,6 - 4,1) 6,0 (1,4 - 6,6) 7,1 (2,4 - 9,4) 9,5 (2,0 - 9,9) 11,2 (3,5 - 12,8) 12,4 (3,5 - 14,2) 16,0 (3,5 - 18,0) 12,4 (3,5 - 14,2) 18,0 (5,0 - 18,5)

Power input cooling

W 1200 1560 2130 2750 3170 5000 4600 3300 5300

Power input heating

W 1400 1620 1990 2640 3100 4800 4340 3300 5000

COP (nominal)

W/W 3.90 3.70 3.30 3.60 3.73 3.61 3.61 3.75 3.60

EER (nominal)

W/W 3.25 3.40 3.21 3.20 3.22 3.21 3.21 3.30 3.21

COP/EER

A/A A/A A/A A/A A/A A/A A/A A/A A/A

Refrigerant prefilling

g 1250 1400 2400 2600 3500 3800 4300 3800 5500

Liquid pipe

inch 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"

Gas pipe

inch 1/2" 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 3/4"

Maximum pipe length

m 20 20 30 30 30 50 50 50 50

Maximum height difference

m 15 15 15 15 15 30 30 30 30

Extra filling per meter

g/m 30 30 60 60 60 60 60 60 60

Sound pressure level

dB(A) 55 56 59 59 61 61 61 61 63

Electrical

Power

V/Hz/Ph 220~240/50/1 380~415/50/3

Nominal current

A 6.40 8.38 9.70 9.7 13.50 15.23 20 9.40 13.38

Compressor power

W 1070 1630 2200 2200 3100 3100 2100 3010 3200

Power cable

mm2 3x2,5 3x4,0 3x4,0 3x4,0 3x4,0 3x4,0 3x6,0 5x2,5 5x2,5

Supply inside

mm2 3x1,0 3x1,0 3x1,0 3x1,0 3x1,0 3x1,0 3x1,0 3x1,0 3x1,0

communication cable

mm2 bij binnenunit bij binnenunit bij binnenunit bij binnenunit bij binnenunit bij binnenunit bij binnenunit bij binnenunit bij binnenunit

fuse

16 20 20 20 25 25 35 16 16

System

Compressor type

Rotary Rotary Rotary Rotary Rotary Rotary Rotary Rotary Rotary

Compressor MFG

Linda Sanyo Mitshibishi Mitshibishi Mitshibishi Mitshibishi Mitshibishi Mitshibishi Mitshibishi

expansion Control

electronic valve electronic valve electronic valve electronic valve electronic valve electronic valve electronic valve electronic valve electronic valve

Auto restart

ja ja ja ja ja ja ja ja ja

Dimensions outdoor unit (LxHxD)

mm 776x320x540 955x396x700 980x427x790 980x427x790 1107x440x1100 1107x440x1100 1085x427x1365 1107x440x1100 1085x427x1365

Netto weight outdoor unit

kg 35 50 63 68 86 95 120 103 127

Range cooling

C -7~43 -7~43 -7~43 -7~43 -7~43 -7~43 -7~43 -7~43 -7~43

Range heating

C -7~24 -7~24 -7~24 -7~43 -7~24 -7~24 -7~24 -7~24 -7~24

PED category

Art 3. Art 3. Cat. I Cat. I Cat. I Cat. I Cat. I Cat. I Cat. I
Remark: Test conditions; Cooling Indoor temp 27°CDB/19°CWB, Outside temp 35°CDB/24°CWB. Heating Indoor temp 20°CDB/15°CWB, Outside temp 7°CDB/6°CWB.
The contained current and power consumption are the values of operation during the test conditions and may be different in practice. Sound pressure level measured in a semi-anechoic room .
J02.370.1f  •  Subject to technical modification