Other Countries
Pricelist request
Copyright
Group Head Quarters • English
Ethics Policy
J03  •  Air cooled water chiller with free coolingdownloads

PHOENIX/FC

Air cooled water chillers with Freecooling for production of cooling water with double screw semihermetic compressors, R407C, cooling capacity 187 - 494 kW

Application

Outside units for HVAC applications like hospitals, shopping center, hotels, offices, ...

Composition

  • Refrigerant R407C
  • Power supply 400/3/50
  • Twin screw compressors with crankcase heater and oil level control
  • Part winding start for reduced current spikes
  • Compressor suction and discharge valves
  • Shell and tube evaporator
  • Independent refrigeration circuits
  • Condensers and fans installed in separate section with aeraulic isolation for the maximum exploitation of Free-Cooling and the maximum overall energy effi ciency of the system
  • Axial fans with crescent shaped blades
  • 3-way modulating valve for Free-Cooling (controlled by microprocessor), water connections within chiller
  • Total Free-Cooling from approximately 10°C below the water outlet temperature
  • Water diff erential pressure switch on evaporator
  • High and low pressure transducers
  • Electronic expansion valve with external equalisation, refrigerant fi lter, sight glass, solenoid valve on liquid line
  • Safety valve (except 0801 - 1101)
  • Microprocessor control with advanced software ensuring optimum control in all conditions
  • Main switch
  • Protection grade IP54
  • SSF fi tted silencers, fl exible tubing and compressor vibration damping

Options

  • Compressor silencing canopy on C version (standard on other version)
  • Electronic termostatic valve
  • Correction capacitor
  • Axial fans with continuos regulation
  • Fused or MCB electrical protection
  • –15 °C ambient temperature version

Versions

  • C, standard acoustic configurations
  • SC, low noise acoustic configurations
  • SF, low noise acoustic configurations with high ambient temperature
  • SSF, very low noise acoustic configurations

Accessories

  • Air fi lters on coils
  • Antivibration dampers
  • Kit for remote control
  • Supervision system kits

Order example

PHFC-2202/C

 

Explanation

 

PHFC = Phoenix free cooling type

2202 = size, see table 

C = Standard amb. 45°C, SC = Low noise amb. 41°C, SF = low noise amb. 47°C, SSF = Super low noise amb. 43°C

Text for tender

Range of free-cooling units is a series of air cooled

packaged water chillers with double screw type compressors, equipped

with an new free-cooling integrated system with independent aeraulic

circuits with very high energy efficiency.

Free-cooling is the best system for obtain high savings in electrical

energy and it is particularly indicated in the industrial process cooling

where the production of water cooled is required all year long.

It consists in to exploit, in winter time and during the intermediate

season, the low temperature of external air to cooling completly or only

a part the water of process cooling is normally cooled through the

compressors.

During free-cooling functioning these chillers use an logical modulated

type where the free cooling of the water can happen every seasons of

the year, with compressors OFF (total free-cooling), or with compressors

partially ON (partial free-cooling).

The free-cooling units have one or two independents cooling

circuits and one compressor for circuit. The refrigerant gas utilized is

R407C.

The management of each free-cooling isentrusted to a

microprocessor control which enable the management of all the

components and the functioning parameters of units; In case of alarm an

internal memory record the functioning conditions at the time that is

happened.

The free-cooling units have power supply 400/3/50, an

protection rating IP54 and are therefore suitables for outdoor

installations.

Top quality brand components are carefully selected for these chillers

that are designed, produced and tested in compliance with ISO9001.

Specifications

PHFC   Mod. 0801 0901 1101 1251 1401 1602 1702 1802 2002 2202
Elektrische voeding / Alimentation électrique   V/Ph/Hz 400 +-10%/3/50
Koelcapaciteit / Puissance frigorifique Free cooling OFF kW 187 218 264 306 362 373 395 412 467 494
Opgenomen vermogen / Puissance absorbée kW 74 87 101 115 131 148 163 177 190 209
Koelcapaciteit / Puissance frigorifique Free cooling ON kW 187 218 264 306 362 373 395 412 467 494
Opgenomen vermogen / Puissance absorbée kW 6 8 8 10 12 12 12 12 14 14
Totaal bij free cooling / Total en free cooling °C -0.20 -1.60 -2 -0.60 0.10 -0.20 -0.80 -1.30 -0.60 -1.30
Geluidsniveau / Niveau sonore   dB(A) 62 63.20 62.60 63.60 65 65.50 65.60 65.70 66.90 66.90
Water verdamper in 15°C / uit 10°C, omgevingstemperatuur 35°C, 30% glycol                        
Geluidsniveau in een vrij veld op 10m afstand van condensor en 1,6m van de grond, tollerantie +- 2 dB. Toestel op volledige capaciteit, met circulatie pomp aan.                        
Eau échangeur entrée 15°C / sortie 10°C, température extérieure 35°C, 30% glycol                        
Niveau acoustique mesuré selon la méthode en champ libre à une distance de 10m (côte condenseur) et à 1,6m du sol. Appareil en plein charge, avec pompe de circulation tournante.                        

Dimensions

PHFC

 

0801

0901

1101

1251

1401

1602

1702

1802

2002

2202

D

[mm]

3675

4590

4590

5490

6425

6425

6425

6425

7360

7360

W

[mm]

2190

2190

2190

2190

2190

2190

2190

2190

2190

2190

H

[mm]

2350

2350

2350

2350

2350

2350

2350

2350

2350

2350

 

[Kg]

2623

3306

3814

4648

5003

5273

5385

6089

6133

6154

J03.300.1V  •  Subject to technical modification