Other Countries
Pricelist request
Copyright
Group Head Quarters • English
Ethics Policy
J03  •  Fan-coil units with EC Brushless motor with Inverterdownloads

AFC-EC-INV

Fan-coil units with EC Brushless motor with Inverter in 10 sizes for a 2-pipe system (FC with 1 coil), 10 sizes for a 4-pipe system (FC with 2 coils), 14 different versions (+ 3 special versions), a wide variety of accessories and a high product flexibility allowing any installation to satisfy all requirements.

Advantages: modulating performances 0-100%, energy saving, CO2 emissions reduction, maximum noise reduction.

Application

  • For cooling and/or heating of hotels, shops, offices,...

Composition

  • Cabinet (for versions VM1-VM2-VM3-VM4-VM5-OM1-OM2-OM3 only): beautiful, smart, modern styled cabinet, standard white colour (similar to RAL 9010) or any other RAL colour on request, thermo acoustic internal insulation, 220 mm depth, air delivery grills
  • Bearing: structure made of extremely thick galvanized steel-sheet with holes for mounting on wall/ceiling + internal thermal-acoustic insulation
  • Drain pan: condensation drain with thermal insulation
  • Coil(s): made of copper pipes and aluminium fins fixed by mechanical expansion, standard connections on the left side; on request (no additional charge) connections on the right side
  • Fan: including 1, 2 or 3 centrifugal fans with double air inlet, statically and dynamically balanced
  • Electric motor: Motor Brushless DC (DC= Direct Current) = Brushless EC (EC= electronic): last generation Electronic Motor, with permanent magnets, Brushless, DC, equipped with the driving electronics (Inverter). IP 40, Class B, electric cables protected by double insulation, 230Vac–1Ph–50/60Hz. Continuous variation 0-100% of the RPM
  • Filter: High efficiency air filter, easily removable and cleanable

Versions

  • With or without cabinet
  • Vertical or horizontal execution
  • Parapet or concealed

Accessories

  • 2 or 4-way control valve available with 3-point modulating actuator
  • Auxiliary drain pan
  • Electrical heater 230V
  • Feets
  • Fresh air intake louver. Available manual version (SAM) and motorized version (SAA)
  • Air supply and air intake straight plenum with air grill suitable to be  connected to all plenums
  • Control panels (wall or built-in)
  • Condensate pump

Technical Data

Sizes

    12 22 32 42 52 62 72 82 92 102
Nominal performances (ref. modulating signal which guarantees “Air Flow FCE Brushless = Air flow of the corresponding asynchronous FC”)
2-pipes

Cooling capacity

Total (1) W 1.500 2.000 2.530 3.020 3.750 4.250 5.520 6.420 7.440 8.790
Sensible (1) W 1.290 1.620 2.070 2.310 2.870 3.230 4.330 4.800 5.600 6.420

Heating capacity (2)

W 3.740 4.910 5.980 6.710 8.160 9.440 12.000 13.300 15.300 17.600

Nominal Air flow (3)

m3/h

370 400 500 550 670 720 1.000 1.050 1.255 1.255

Water flow (4)

Total (1)

l/h

258 344 436 520 645 731 950 1.105 1.280 1.512
Sensible (1) l/h 322 423 515 578 702 812 1.032 1.144 1.316 1.514

Water pressure drops (5)

Cooling kPA

13.1

16.30 18.50 20.80 22.60

24.1

24.50

27.1

28.1

27.70
Heating kPA 15.90 19.20

20.1

20 20.90 23.20 22.60 22.70 23.20 21.70

Sound levels (6)

Nominal dB(A) 36 39 41 43 34 36 42 43

46

46

Current input (operating values)

19W-0,15A 25W-0,19A 27W-0,20A 34W-0,25A 23W-0,16A 26W-0,20A 46W-0,31A 53W-0,35A 73W-0,48A 73W-0,48A

Reference control signal (10)

5,8 Vdc 6,8 Vdc 7,1 Vdc 8,0 Vdc 5,7 Vdc 6,2 Vdc 8,0 Vdc 8,5 Vdc 10 Vdc 10 Vdc

Power supply

Power: 230Vac/1Ph/50/60Hz Signal: 0-10Vdc

   

4-pipes

Cooling capacity

Total (1) W 1.450 1.940 2.470 2.920 3.650 4.110 5.390 6.230 7.440 8.790
Sensible (1) W 1.240 1.570 2.020 2.220 2.780 3.110 4.210 4.640 5.600 6.420

Heating capacity (2)

W 1.880 1.980 3.180 3.350 4.380 4.550 6.290 6.460 8.090 8.090

Nominal Air flow (3)

m3/h

350 380 480 520 640 680

960

1.000 1.255 1.255

Water flow (4)

Total (1) l/h 250 334 425 503 628 707 928

1.072

1.280 1.512
Sensible (1) l/h 162 171 274 289 377 392 541 556 696 696

Water pressure drops (5)

Cooling kPA

12.3

15.40 17.60 19.50 21.40

22.5

23.40

25.1

28.1

27.70
Heating kPA 7.30

8.10

11.7

13 21.30 23

41.1

43.40 38.60 38.60

Sound levels (6)

Nominal dB(A) 34 36 40 42 33 34 41 42 46 46

Current input (operating values)

16W-0,13A 23W-0,17A 26W-0,19A 30W-0,22A 22W-0,15A 23W-0,17A 42W-0,29A 46W-0,31A 73W-0,48A 73W-0,48A

Reference control signal (10)

5,5 Vdc 6,1 Vdc 6,9 Vdc 7,5 Vdc 5,4 Vdc 5,9 Vdc 7,6 Vdc 8,0 Vdc 10 Vdc 10 Vdc

Power supply

Power: 230Vac/1Ph/50/60Hz Signal: 0-10Vdc

Technical data refer to the following conditions: Standard unit - Atmospheric pressure 1013 mbar - Power supply 230Vac/1Ph/50Hz.

(1) (2) (3) (4) (5): Nominal technical data , ref. air flow (3) to the (10) indicated signal and unit with free air flow (External static pressure ESP=0Pa).

(1) Cooling: Air temp.: 27°Cd.b., 19°Cw.b. - Entering/leaving water temp. 7/12°C - Nominal speed (ref. Signal (10) = air flow (3)). For different air flows (ex. Max and/or Min speed and/or ESP > 0Pa) see (8)+(9): ref. nominal air flows, entering water temp. 7°C and water flow as for nominal speed (4).

(2) Heating: Air temp.: 20°C - Entering/leaving water temp. 70/60°C - Nominal speed (ref. Signal (10) = air flow (3)). For different air flows (ex. Max and/or Min speed and/or ESP > 0Pa) see (8)+(9): ref. nominal air flows, entering water temp. 70°C and water flow as for nominal speed (4).

(1) (2) (9) Cooling and Heating capacities: Data calculated by SW and measurements made in calorimetric room ref. UNI 7940 part 1°-2° , UNI-EN 1397/2001 standards.

(3) (8) Air flow and Static pressure: Nominal data measured with casing ref. AMCA210-74 fig.12 standards and plenum + diaphragm ref. CNR-UNI10023 standards.

(8) Air flow curves: Max= 10Vdc signal ; Med= nominal signal (10), (size 90-100: x0,8Max) ; Min= 3Vdc signal (ref. SW "Constant Voltage" + constant ratio).

(6) Sound Levels: Free field sound pressure, 2 m distance. Data calculated based on sound power measured in riverberation room ref. ISO 3741 - ISO 3742 standards.

(7) Electrical data: MAX value of motor label = reference value for the electrical system design. All the elect. data measured with Wattmeter Jokogawa WT110.

Sizes

12

22

32

42

52

62

72

82

92

102

ECO (3Vdc)

Expected operating conditions (balance "Unit's performances = required performances")

Air flow; Sound Levels

240 m3/h ; 23 dB(A)

285 m3/h ; 26 dB(A)

424 m3/h ; 22 dB(A)

514 m3/h ; 24 dB(A)

536 m3/h ; 25 dB(A)

Current input (operating values)

9W - 0,09A 9W - 0,10A 10W - 0,09A 11W - 0,10A 11W - 0,09A

RANGE 10-1Vdc

MAX performances ref. 10Vdc signal; MIN ref. 1Vdc (for signal <1Vdc the unit is OFF)

Cooling cap.

Total W 1.810-880 2.320-1.130 2.830-1.400 3.220-1.600 4.630-2.130 5.070-2.330 6.010-3.060

6.820-3.470

7.440-3.780 8.790-4.460

Heating capacity

W 4.680-1.970 5.860-2.470 6.840-2.940 7.250-3.120 10.510-4.130 11.650-4.580 13.280-5.900 14.300-6.350 15.300-6.780 17.600-7.800

Air flow

m3/h

537 - 127

625 - 153

1.021 - 215 1.184 - 306 1.255 - 323

Sound Levels

dB(A)

45 - 10

47 - 10

45 - 12

46 - 9

46 - 11

Current input (operating values)

48-6W ; 0,32-0,07A 54-6W ; 0,36-0,07A 65-6W ; 0,44-0,07A 74-6W ; 0,49-0,08A 73-6W ; 0,48-0,07A

Dimension table

12 22

32

42

52

62

72

82

92

102
L x H x S L 670 x H 470 x S 220 L 870 x H 470 x S 220 L 1.070 x H 470 x S 220

L 1.270 x H 470 x S 220

L 1.470 x H 470 x S 220
A - B A=400 ; B=425 A=600 ; B=625 A=800 ; B=825 A=1.000 ; B=1.025 A=1.200 ; B=1.225

F – Feet

W.C. - Water Connections

D.P. - Drain Pipe

C.D.F. - Condensation Drain Funnel

A.D.P. - Auxiliary Drain Pan (optional)

A.I.F.S. - Air Intake Feet Support with grill - versions VM2 - OM2

* - Version with cabinet

** - Version without cabinet

*** -  Female gas water coil connections

Prices

About prices call our sales representatives.
J03.400.B  •  Subject to technical modification