Data referred to the following conditions:
All the data provided meets standard EN 14511:2008 and refers to an available head of 50 Pa. When in cooling mode it is possible that the unit is operating at a reduced flow to ensure a specific humidity for the air introduced into the environment in keeping with the setpoint
(1) A7 External air temperature 7°C D.B. / 6°C W.B.; Exhaust air temperature: 20°C D.B. / 15°C W.B.
A-5 External air temperature -5°C D.B. / -5.4°C W.B.; Exhaust air temperature: 20°C D.B. / 15°C W.B.
A30 External air temperature 30°C D.B. / 22°C W.B.; Exhaust air temperature: 27°C D.B. / 19°C W.B.
A35 External air temperature 35°C D.B. / 24°C W.B.; Exhaust air temperature: 27°C D.B. / 19°C W.B.
(2) Capacity referring to operation in heating mode in conditions A-5. Important: the COP and EER already include the fan power and input. This information is provided for the purposes of energy certification programmes. If this information is taken into account, the COP used must be the COP without the fan power input
(3) In places where the outdoor air temperature falls below -5°C for a large number of hours per year, we recommend using EHPCX accessory - ducted heater kit
(4) With RH = 40%; in parentheses, the limit at which a specific humidity of 10.5 g/kg is guaranteed for the air introduced into the environment, with a 50% reduction in the maximum flow
(5) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field coditions
A. Air filter
It purifies the fresh air before introducing it into the rooms
B. Internal exchanger
It transfers energy (heat / cool) to the fresh air. Finned direct expansion exchanger with copper tubes and aluminium fins
C. Supply fan
It blows treated air in the rooms. Centrifugal fan powered in direct current directly coupled to the electric motor
D. Compressor
It allows to “move” the heat from the exhaust to the fresh air. Ermetic rotary compressor
E. External exchanger
It recovers energy (heat / cool) from the exhaust air. Finned direct expansion exchanger with copper tubes and aluminium fins
F. Exhaust air fan
It rejects the unhealthy air outdoors. Centrifugal fan powered in direct directly coupled to the electric motor
G. Electrical remote panel
It is possible to remove the electrical panel and make it remote to facilitate the installation
MAIN OPTIONS
1. High-efficiency filtration
The electronic filter (efficiency equivalent to H10) increases the purity of inlet air, reducing the costs of energy used for ventilation
2. Resistance from 1,5 to 3 kW
It allows to maintain a supply temperature next to the comfort temperature without intervening on the air flow decreasing
3. Immersed electrode humidifier
For the outdoor air humidifcation
4. Exhaust air filter
For the recovery coil protection on the exhaust air