J13  •  Active chilled beamsdownloads

ACB-S

Active chilled beams, square. These active chilled beams fit perfectly into the falso ceiling, with its width of 300 mm. This air handling unit ensures you of a highly comfortable installation, chractarized by low air velocities and a small vertical gradient.

 

Energy friendly product because of cooling with high temperatures. Combination with heat pump system is possible.

 

Please always take into account when designing an installation with chilled beams, the right water temperature is selected. Too low water temperatures will give the risk of leakage of condensing water dripping out of the units. Therefore a good controlling of both temperature and relative humiity in de rooms is important.

Application

  • Cooling, heating and ventilation of working environments

Composition

  • Steel
  • Front plate can be opened for cleaning of the heat exchanger
  • Heat exchanger Cu/Al
  • Horizontal water connection standard
  • Side connection voor primary air Ø125 mm

Colour

  • White, RAL9010
  • Other colours on request

Versions

  • Nozzle type B, C or D dependent on quantity of primary air
  • 4-way, 3-way or 2-way pattern for supplied air

Accessories

  • Sonoflex25 Ø127 mm
  • Constant volume damper KVR-125

Articles

Article number Module [mm] Cooling Heating Nozzle type Number of supply areas
  J130200600001600x600 yes yes B 4
  J130200600002600x600 yes yes B 3
  J130200600003600x600 yes yes B 2
  J130200600004600x600 yes yes C 4
  J130200600005600x600 yes yes C 3
  J130200600006600x600 yes yes C 2
  J130200600007600x600 yes yes D 4
  J130200600008600x600 yes yes D 3
  J130200600009600x600 yes yes D 2

Order example

  • ACB-S B/4/RAL9010

Explanation:

ACB-S = productname

B = nozzle type

4 = numbe extract directions

RAL9010 = finishing

Quick selection

Luchtzijdige gegevens

Waterzijdige gegevens

Supply airquantityprimary

Static pressure loss Cooling throw Heating throw Sound Power Air cooling capacity Room to Air Water quantity Cooling Heating
          ΔT = 8K ΔT = 10K   druk verl. ΔT = 8,5K ΔT = 9,5K ΔT = 11K druk- verlies ΔT = 20K ΔT = 30K
m3/h Pa m m dB(A) Watts l/h kPa Watts kPa Watts
Nozzle B
30 44 1.10 1.30 30 82 103 70 0.70 146 157 157 0.40 422 588
100 1.40 173 186 186 0.90 497 692
130 2.20 195 210 210 1.50 558 778
35 60 1.30 1.50

33

96 120 70 0.70 181 196 239 0.40 453 631
100 1.40 216 233 285 0.90 534 744
130 2.20 244 263 321 1.50 601 837
40 77 1.50 1.70 35 110 137 70 0.70 225 243 298 0.40 481 670
100 1.40 268 289 354 0.90 569 792
130 2.20 303 328 400 1.50 640 892
Nozzle C
50 36 1.20 1.40 22 137 171 70 0.70 160 173 212 0.40 468 651
100 1.40 191 206 252 0.90 552 789
130 2.20 216 233 284 1.50 621 865
60 51 1.50 1.70 26 164 205 70 0.70 219 227 249 0.40 506 705
100 1.40 252 261 295 0.90 599 835
130 2.20 280 293 335 1.50 676 941
70 69 1.70 2 30 192 240 70 0.70 230 249 305 0.40 541 753
100 1.40 276 298 364 0.90 642 894
130 2.20 313 338 413 1.50 725 1009
Nozzle D
80 47 1.50 1.70 32 219 274 70 0.70 186 201 245 0.40 501 698
100 1.40 222 239 293 0.90 593 827
130 2.20 251 271 332 1.50 669 932
90 59 1.70 2 36 246 308 70 0.70 211 229 278 0.40 528 735
100 1.40 252 272 332 0.90 628 872
130 2.20 285 308 376 1.50 707 984
110 88 2.10 2.50 42 301 376 70 0.70 261 282 345 0.40 576 802
100 1.40 314 338 414 0.90 685 954
130 2.20 356 385 470 1.50 775 1080
130 122 2.60 3 48 356 445 70 0.70 314 339 415 0.40 618 861
100 1.40 378 409 499 0.90 738 1027
130 2.20 431 465 569 1.50 836 1164
Data: EN15116 (Ventilation in buildings - Chilled beams - Testing and rating of active chilled beams)

J13.02  •  Subject to technical modification